banner

CIC-152 Dual Control Dosing/Injection TDS/EC Controller

Delivery term:The date of payment from buyers deliver within days
  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Beijing

  • Validity to:

    Long-term effective

  • Last update:

    2017-11-24 05:10

  • Browse the number:

    98

Send an inquiries
Company Profile
Qingdao Tlead International Co. Ltd
By certification [File Integrity]
Contact:

tlead(Mr.)  

Telephone:

Area:

Beijing

Address:

2606, 7080 Center, No.17 KunShan Road, Qingdao, Shandong, China (266071)

Website: http://tlead.mingzhuqizhong.com/
Product details
Model Number: CIC-152 Brand Name: TLead Key Specifications/Special Features: Monitors and controls dosing or injection systemsLarge, bright tri-color LED displayTwo adjustable set points keep TDS levels within a range (maximum and minimum TDS/EC levels)Minimum and maximum control points will activate relay controls via switching dry contactsThe CIC-152 can control two different devices (pump and valve)
  • Two alarms (maximum and minimum levels) can be set independently of the control points
  • Digital calibration
  • On-screen temperature display
  • On-screen range and control indicator lights (green, yellow or red)
  • Installs easily in minutes
  • Includes one sensor probe (no extra cost)
  • Protective cover also available (sold separately)
  • Available with the NaCl conversion factor (model CIC-152-N) or the 442TM conversion factor (model CIC-152-4)
  • TDS range: 0 - 5,000ppm (CIC-152-N): 0 - 8,500ppm (CIC-152-4)
  • EC range: 0 - 9,999S
  • Temperature range: 1-80°C; 33-176°F
  • Accuracy: ±2% (of the reading)
  • Resolution: 0.1 ppm (0-999); 1 ppm (1000-9999)
  • ATC: (1 - 80°C)
  • Calibration: digital (by push button)
  • Factory calibration: 1413 S
  • Conversion factor: CIC-152-N: NaCl (avg. 0.5); CIC-152-4: 442 (0.4-0.7)
  • Set points: adjustable by push button
  • Control point 2: maximum TDS limit
  • Control point 1: lower TDS level
  • Relay control: unit will transmit an analog signal (simple switch) via open or closed contacts to a device (pump/valve) when the ppm/S level reaches the maximum TDS/EC limit (control point 2) or the minimum TDS/EC limit (control point 1)
  • The contacts are switched back to the normal position once the TDS returns to the acceptable range
  • Relay voltage: 5V (attached devices must have their own power supply)
  • Alarm: two independent alarms (set by user)
  • Display: bright 5/8" LED display
  • Probe: 1/2" bushing (NPT), 3 meter (9.8 ft) shielded cable (model SP-1-PSC)
  • Power supply: AC 110V/AC 220V
  • Dimensions: 7.2 x 7.2 x 11.1cm (2.8 x 2.8 x 4.4 inches)
  • Monitor weight: 241g (8.5oz)
  • Total (shipping) weight: 610g (1lb 5.5oz)
  • Shipping Information:
    • FOB Port: Qingdao
    Main Export Markets:
    • North America
    • Central/South America
    • Asia
    • Australasia
    • Eastern Europe
    • Mid East/Africa
    • Western Europe